Goodrive20-EU Series VFD
Function parameters
-59-
Function
code
Name
Description
Default Modify
61: PID pole switching
62
–63: Reserved
When the terminal acts as ACC/DEC time
selection, you need to select four groups of
ACC/DEC time through state combinations of
these two terminals.
Terminal 1
(21)
Terminal 2
(22)
ACC/DEC time
setting
Parameters
OFF
OFF
ACC/DEC time 1
P00.11/
P00.12
ON
OFF
ACC/DEC time 2
P08.00/
P08.01
OFF
ON
ACC/DEC time 3
P08.02/
P08.03
ON
ON
ACC/DEC time 4
P08.04/
P08.05
P05.10
Input terminal
polarity
selection
The function code is used to set the polarity of
the input terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT8
BIT7
BIT6
BIT5
BIT4
HDI
S8
S7
S6
S5
BIT3
BIT2
BIT1
BIT0
S4
S3
S2
S1
Setting range: 0x000
–0x1FF
0x000
○
P05.11
Switch filter
time
Set the sample filter time of S1
–S4 and HDI
terminals. If the interference is strong, increase
the parameter to avoid wrong operation.
0.000
–1.000s
0.010s
○
P05.12
Virtual terminal
setting
0x000
–0x1FF (0: Disabled, 1: Enabled )
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: S5 virtual terminal
BIT5: S6 virtual terminal
BIT6: S7 virtual terminal
BIT7: S8 virtual terminal
BIT8: HDI virtual terminal
0x000
◎