Fault
code
Fault type
Possible cause
Solutions
OH2
[16] Inverter
module
overheat
temperature;
Check and reconnect;
Change the power;
Change the power unit;
Change the main control
panel.
EF
[17] External
fault
SI external fault input
terminals acts.
Check the external device
input.
CE
[18] 485
communication
fault
The baud rate setting is
incorrect;
Fault occurs to the
communication circuit;
The communication
address is wrong;
There is strong
interference to the
communication.
Set proper baud rate;
Check the wiring of
communication connection
interface;
Set proper communication
address;
Chang or replace the
wiring or improve the
anti-interference capability.
ItE
[19] Current
detection fault
The connection of the
control board is not good;
Assistant power is bad;
Hall components is
broken;
The magnifying circuit is
abnormal.
Check the connector and
plug wire again;
Change the hall;
Change the main control
panel.
tE
[20] Motor
autotuning fault
The motor capacity does
not match with VFD
capacity;
The rated parameter of the
motor is set improperly;
The deviation between the
parameters from autotune
and the standard
parameter is huge;
Autotune overtime.
Change the VFD model;
Set the rated parameter
according to the motor
nameplate;
Empty the motor load;
Check the motor
connection and set the
parameter;
Check if the upper limit
frequency is above 2/3 of
the rated frequency.
EEP
[21] EEPROM
operation fault
Error occurred to R/W of
the control parameter;
EEPROM is damaged.
Press STOP/RST to reset;
Change the main control
panel.