Goodrive20-EU Series VFD
Function parameters
-65-
P06 group Output terminals
Function
code
Name
Description
Default Modify
P06.01
Y1 output
selection
0: Invalid
1: In operation
2: Forward rotation operation
3: Reverse rotation operation
4: Jogging operation
5: The VFD fault
6: Frequency level test FDT1
7: Frequency level test FDT2
8: Frequency reached
9: In zero-speed operation (output in running
state)
10: Upper limit frequency reached
11: Lower limit frequency reached
12: Ready for operation
13: Pre-magnetizing
14: Overload pre-alarm
15: Underload pre-alarm
16: Completion of simple PLC stage
17: Completion of simple PLC cycle
18: Setting count value arrival
19: Defined count value arrival
20: External fault valid
21: Zero-speed output (output in both running
and stopping states)
22: Running time arrival
23: Modbus communication virtual terminals
output
24
–25: Reserved
26: Establishment of DC bus voltage
27: STO action
28
–30: Reserved
0
○
P06.03
Relay RO1
output
selection
1
○
P06.04
Relay RO2
output
selection
5
○
P06.05
Polarity
selection of
output
terminals
The function code is used to set the pole of the
output terminal.
When the current bit is set to 0, input terminal is
positive.
When the current bit is set to 1, input terminal is
negative.
0
○