Fault
code
Fault type
Possible cause
Solutions
OV2
[8] Overvoltage
during
deceleration
feedback;
No brake components;
Braking energy is not
open.
short or the VFD starts
during the rotation of the
motor or it is necessary to
install dynamic braking
components;
Install the brake
components;
Check the setting of
related function codes.
OV3
[9] Overvoltage
during constant
speed running
UV
[10] Bus
undervoltage
The voltage of the power
supply is too low.
Check the input power of
the supply line.
OL1
[11] Motor
overload
The voltage of the power
supply is too low;
The motor setting rated
current is incorrect;
The motor stall or load
transients is too strong.
Check grid voltage;
Reset the rated current of
the motor;
Check the load and adjust
the torque lift.
OL2
[12] VFD
overload
Acceleration is too fast;
Restart the rotating motor
Grid voltage is too low;
The load is too heavy;
The rated power is much
larger than the power
actually needed.
Increase acceleration
time;
Avoid restarting after
stopping;
Check the grid voltage;
Select a VFD with larger
power;
Select a proper motor.
SPI
[13] Phase loss
on input side
Phase loss or fluctuation of
input R, S, T.
Check input power
Check installation wiring.
SPO
[14] Phase loss
on output side
U, V, W phase loss output
(or serious asymmetrical
three phase of the load).
Check the output wiring;
Check the motor and
cable.
OH1
[15] Rectifier
module
overheat
Air duct is blocked or fan is
damaged;
Ambient temperature is
too high;
The time of overload
running is too long.
Refer to the overcurrent
solution;
Redistribute;
Dredge the wind channel
or change the fan;
Lower down the ambient