Goodrive20-EU Series VFD
Function parameters
-89-
Function
code
Name
Description
Default Modify
P10.14
Multi-step
speed 6
Output frequency
Terminal 1
(16)
Terminal 2
(17)
Terminal 3
(18)
Terminal 4
(19)
When terminal1= terminal 2= terminal 3=
terminal 4=OFF, the frequency input manner is
selected via code P00.06 or P00.07. When all
terminals aren't off, it runs at multi-step which
takes precedence of keypad, analog value,
high-speed
pulse,
PLC,
communication
frequency input. Select at most 16 steps speed
via the combination code of terminal 1, terminal
2, terminal 3, and terminal 4.
The start-up and stopping of multi-step running is
determined by function code P00.06, the
relationship between
terminal 1 (16) terminal 2 (17),terminal 3 (18),
terminal 4 (19) and multi-step speed is as
following:
Terminal 1 OFF ON
OFF ON OFF ON OFF ON
Terminal 2 OFF OFF
ON
ON OFF OFF ON ON
Terminal 3 OFF OFF OFF OFF ON ON ON ON
Terminal 4 OFF OFF OFF OFF OFF OFF OFF OFF
step
0
1
2
3
4
5
6
7
Terminal 1 OFF ON
OFF ON OFF ON OFF ON
Terminal 2 OFF OFF
ON
ON OFF OFF ON ON
Terminal 3 OFF OFF OFF OFF ON ON ON ON
Terminal 4 ON ON
ON
ON ON ON ON ON
Setting
range
of
P10.(2n,
1<n<17):
-100.0
–100.0%
0.0%
○
P10.15
Running time
of step 6
0.0s
○
P10.16
Multi-step
speed 7
0.0%
○
P10.17
Running time
of step 7
0.0s
○
P10.18
Multi-step
speed 8
0.0%
○
P10.19
Running time
of step 8
0.0s
○
P10.20
Multi-step
speed 9
0.0%
○
P10.21
Running time
of step 9
0.0s
○
P10.22
Multi-step
speed 10
0.0%
○
P10.23
Running time
of step 10
0.0s
○
P10.24
Multi-step
speed 11
0.0%
○
P10.25
Running time
of step 11
0.0s
○
P10.26
Multi-step
speed 12
0.0%
○
P10.27
Running time
of step 12
0.0s
○
P10.28
Multi-step
speed 13
0.0%
○
P10.29
Running time
of step 13
0.0s
○
P10.30
Multi-step
speed 14
0.0%
○
P10.31
Running time
of step 14
0.0s
○
P10.32
Multi-step
speed 15
0.0%
○
Содержание Goodrive20-EU VFD Series
Страница 1: ......
Страница 173: ...6 6 0 0 1 0 0 4 8 4...