Goodrive20-EU Series VFD
Function parameters
-87-
Function
code
Name
Description
Default Modify
current running direction, the internal will output
0 forcedly.
1: Opposite to the main reference direction
Hundreds place:
0: Limit as per the maximum frequency
1: Limit as per A frequency
Thousands place:
0: A+B frequency, main reference A frequency
source buffering ACC/DEC is invalid;
1: Main reference A frequency source buffering
ACC/DEC is valid and the ACC/DEC is
determined by P08.04.
P09.15
PID command
acceleration/
deceleration
time
0.0
–1000.0s
0.0s
○
P09.16
PID output filter
time
0.000
–10.000s
0.000s
○
P09.17
Low frequency
proportional
gain (Kp)
0.00
–100.00
1.00
○
P09.18
Low frequency
integral time
(Ti)
0.00
–10.00s
0.10s
○
P09.19
Low frequency
differential time
(Td)
0.00
–10.00s
0.00s
○
P09.20
Low point
frequency of
PID parameter
switching
0.00Hz
–P09.21
When the ramp frequency is no greater than
P09.20,
current
PID
parameters
are
P09.17
–P09.19. When the ramp frequency is no
less than P09.21, current PID parameters are
P09.04
–P09.06. The medium frequency range is
the linear interpolation values between the two
PID parameter groups.
5.00Hz
○
P09.21
High point
frequency of
PID parameter
switching
P09.20
–P00.03
10.00Hz
○
Содержание Goodrive20-EU VFD Series