Alarm code
24
Abnormal operation of the thermistor for the outdoor unit heat exchanger liquid pipe (Te/
Tchg).
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
If an anomaly is detected in the thermistor, check the thermistors as follows:
* This alarm is indicated when the thermistor is short-circuited (less than 0.2 kΩ) or cut (greater than 840 kΩ) for eight
minutes during operation.
* These thermistors are installed as shown in the following figure.
Yes
Yes
Connect it.
No
Faulty Thermistor
Faulty PCB1
No
Are thermistors connected to
THM10 (Te) or THM17 (Tchg)
on PCB1?
Is resistance of the
thermistor between
0.2k
Ω
and 500k
Ω
?
Refer to "Alarm Code 11"
for thermistor resistance.
If this thermistor is faulty, this alarm is indicated.
Te: Thermistor for Outdoor Liquid Pipe
Tchg: Thermistor for Super Cooling Main Line
PCB1: Control PCB in Outdoor Unit
Te Thermistor
(THM10)
Thermistor Holder
Butyl Sheet
Butyl Sheet
Plastic Sheet
Te Thermistor (THM10)
Tchg Thermistor (THM17)
Evaporation
Liquid Pipe
< Details for Thermistor >
Tchg Thermistor
(THM17)
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Faulty
Outdoor Unit
Liquid Pipe
Thermistor
Check resistance.
Replace thermistor
if faulty.
Fault
Check wiring to PCB1.
Repair wiring and
connections.
Incorrect Connection
Replace PCB1 and
check operation.
Replace PCB1 if faulty.
Faulty PCB1
8 Troubleshooting
203
SMGB0065 rev. 1 - 12/2010