5.2.7 Heating operation (continued)
Pressing
Auto-Louver
Switch
3
Alternately
Start of
Auto-Louver
Stop of
Auto-Louver
only for Air Panel
or Indoor Unit
with Auto-Louver
Pressing
RUN/STOP
Switch
I.U.:
O.U.
Indoor Unit
Outdoor Unit
Heat
Rejection
Operation
Slow Indoor Fan MIF Speed
< 50°C
< 2 min.
after 2 min.
> 40°C
< 40°C
Indoor Fan Motor MIF : OFF
Indoor Unit
Discharge Air
Temp.
> 50°C
STOP
Power to PCB in I.U.: OFF
Electronic Expansion Valve in I.U. and O.U.:
Fixed Opening
RUN LED: OFF. HEAT, Set Air Flow &
Set Temp. Indication: Continuously ON
LCD Indication: OFF
Power to
I.U.: OFF
Operation
at Slow Indoor
Fan Speed
Indoor
Unit Discharge
Air Temp.
5 Control system
103
SMGB0065 rev. 1 - 12/2010