Item
Part Name
Item
Part Name
PCB1
Control PCB in Outdoor unit
PCB2
Inverter PCB
IPM
Transistor module
FANM1
Fan controller
DM
Diode module
DCL1, 2
Reactor
NF1~15
Noise filter
R1, 2
Resistor
RS1, 2
Resistor for starting
C
Capacitor
CB1 , 2, 3
Capacitor
CS1, 2
Capacitor
TB1, 2, 3
Terminal board
CMC1, 2
Magnetic contactor for compressor motor
EF1, 2, 3, 4, 11
Fuse
EFR1
Fuse on PCB1
CT2, CTU, CTV
Current sensor
ZNR
Surge Absorver
10.16.2 Removing the PCB2 for the inverter
D A N G E R
•
Turn OFF all the power source switches.
•
Do not touch any electrical component if the LED201 (Red) of the PCB2 is ON. Touching them could cause an
electric shock.
1
Disconnect all the wiring connected to the PCB2 -A-.
2
Disconnect all the power supply lines of the transistor module
-E- (U, V, W) and direct the wiring from the current sensor. Also
disconnect the wiring for N, P and C.
3
Remove the three M3 screws -B-, remove the bushes -C- and
the collars -D- of the PCB2. When fitting the PCB2 make sure
that the bushes and the collars are well fixed.
N O T E
•
Match the numbered terminals with the band marked with numbers when reassembling. If they are connected
incorrectly, this may cause a malfunction and damage the electrical components.
•
Check to ensure that the electrical wiring does not get caught between the electrical components and the
mounting plate when you fit the PCB2.
10.16.3 Removing the diode module and transistor module
D A N G E R
•
Turn OFF all the power source switches.
•
Do not touch any electrical component if the LED201 (Red) of the PCB2 is ON. Touching them could cause an
electric shock.
A
F
B
C
E
D
A
10 Servicing
325
SMGB0065 rev. 1 - 12/2010
10