6.3 Function setting
1
This setting must be carried out during stoppage of the outdoor unit. Set DSW4-#4 of the outdoor unit PCB to ON position
before performing in order to prevent the compressor from being activated.
2
Press PSW1 for more than 3 seconds.
”Menu” will be displayed on the 7-segment display. The menu indicates the changes by pressing PSW2 or PSW4 and
displays them in the following order:
Selection of the function setting mode is indicated by the “Func”
mode on the 7-segment display.
Arrangement of push switches on PCB1
PCB1
211
20CHG
52C1
Fan
SEG1
CH2
20F2
20A2
52C2
CH1
20A1
20B
20C
20F1
X2
X1
212
SEG2
PSW5
PSW1
PSW4
PSW2
PSW3
7-Segment
Display
7-Segment Display
“ioST” (External input and output setting)
By pressing the push-switches PSW3 (►) and PSW5 (◄), the function No. can be selected. PSW4 (▼): forward, PSW2
(▲): backward.
Fill out the selected function setting No. in the space of the table as shown (SET).
<Example>
1
Item
SEG2
SEG1
SET
1
Input Setting 1
CN17 [1-2 pin]
i1
1
2
Input Setting 2
CN17 [2-3 pin]
i2
2
3
Input Setting 3
CN18 [1-2 pin]
i3
3
4
Output Setting 1
CN16 [1-2 pin]
o1
1
5
Output Setting 2
CN16 [1-3 pin]
o2
2
(Setting before shipment)
Before shipping, the input/output function settings are specified to each input/output terminal according to above table.
The details of function No. and external input/output settings are as shown below.
Setting of external input and output function
Function No.
Input
Output
1
Fixing heating operation mode
Operation signal
2
Fixing cooling operation mode
Alarm signal
3
Demand stoppage
Compressor ON signal
4
Outdoor fan motor Start/Stop
Defrost signal
5
Forced stoppage
-
6
Demand current control 40%
-
“CHEC”
“ioST”
“Func”
6 Optional functions
123