Alarm code
22
Abnormal operation of the thermistor for outdoor air temperature (outdoor unit ambient
thermistor).
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the thermistor is short-circuited (less than 0.2 kΩ) or cut (greater than 500 kΩ) during
the operation.
Yes
Yes
Connect it.
No
Faulty Thermistor
Faulty PCB1
No
Is it connected to
THM7 (Ta) of PCB1?
Is resistance of THM7
between 0.2k
Ω
and
500k
Ω
?
Refer to "Alarm Code 11"
for thermistor resistance.
PCB1: Control PCB in Outdoor Unit
Outdoor Unit
Ambient Thermistor
(THM7)
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Faulty
Outdoor Unit
Ambient
Thermistor
Check resistance.
Replace thermistor
if faulty.
Fault
Check wiring to PCB1.
Repair wiring and
connections.
Incorrect Connection
Replace PCB1 and
check operation.
Replace PCB1 if faulty.
Faulty PCB1
8 Troubleshooting
201
SMGB0065 rev. 1 - 12/2010
8