Compressor Pressure/Frequency Indication
Discharge Pressure
(High) (x 0.1 MPa)
20
Suction Pressure
(Low) (x 0.01 MPa)
21
Control Information
22
Operation
Frequency (Hz)
23
Outdoor Unit Code
25
Refrigerant Cycle
Number
26
Refrigerant Cycle
Number
27
Indoor Unit Capacity
24
The total current is indicated when several
compressors are running.
In case of inverter compressor, the running current
of primary side of inverter is indicated.
Capacity Code of Indoor Unit
06
08
10
13
14
16
18
20
22
26
32
40
64
80
0.8
1.0
1.3
1.5
1.8
2.0
2.3
2.5
2.8
3.0
4.0
5.0
8.0
10.0
Indication Code
Equivalent Capacity (HP)
J3: 01 to 16
(01: when shipment (DSW5), Decimal Indication)
J4: 00 to 0F
(00: when shipment (DSW5), Indication with 16 numbers)
In case of models without Expansion Valve (MV2),
the same figure is indicated.
This is an indication for internal information for the remote
control switch. This does not have any specific meaning.
This is an indication for frequency of Inverter.
The capacity of the indoor unit is indicated as shown
in the table below.
n
Indoor Unit Capacity Indication
Outdoor Unit
Expansion Valve
MV1 Opening (%)
29
Outdoor Unit
Expansion Valve
MV2 Opening (%)
30
Outdoor Unit
Expansion Valve
MVB Opening (%)
31
Indoor Unit
Expansion Valve
Opening (%)
28
Expansion Opening Indication
Compressor
Running Current (A)
32
Estimated Electric Current Indication
Temperature Indication
Returns to Temperature Indication
"n" indicates total number of indoor units;
n = ~ , , , , , , ,
(10) (11) (12) (13) (14) (15) (16)
Contents of Check mode 2
The latest data for the three first indoor units that are connected in series are indicated when there are more than three
indoor units connected to one remote control switch.
8 Troubleshooting
242