Alarm code
12
Abnormal operation of thermistor for indoor unit discharge air temperature (air outlet
thermistor).
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the thermistor is short-circuited (less than 0.24 kΩ) or cut (greater than 840 kΩ) during
the cooling or heating operation. The system automatically restarts when the fault is eliminated.
Yes
Connect it.
No
Refer to "Alarm Code 11"
for thermistor resistance.
Faulty PCB
Is the thermistor connected
to THM2 of PCB?
Yes
Faulty Thermistor
No
Is resistance of THM2
between 0.24k
Ω
and 840k
Ω
?
Thermistor
for Air Outlet
Temperature
(THM2)
In Case of 4-Way Cassette Type
PCB1: Control PCB in Outdoor Unit
PCB: Indoor Unit PCB
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Faulty Air Outlet
Thermistor
Check resistance.
Replace thermistor
if faulty.
Fault
Check wiring to PCB.
Connect wiring
correctly.
Incorrect Connection
Replace PCB and
check operation.
Replace PCB if faulty.
Faulty PCB
8 Troubleshooting
194
SMGB0065 rev. 1 - 12/2010