Alarm code
54
Abnormal Inverter fin temperature.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* In the case that the Inverter fin temperature anomaly occurs three times in thirty minutes, this alarm is indicated on
the third time (retry operation is carried out up to second time the anomaly occurs).
Activation condition: this alarm operation is indicated when the Inverter fin thermistor temperature for the transistor
module is greater than 90 °C.
Restart operation.
Does it trip soon?
Is the heat exchanger of
outdoor unit clogged?
No
Replace the PCB2. *1)
Remove clogging.
Yes
Yes
No
Check the thermistor.
Normal
Faulty
Replace the thermistor.
Replace the PCB2. *1)
Check the thermistor.
Normal
Faulty
Replace the thermistor.
PCB1: Control PCB in Outdoor Unit
PCB2: Inverter PCB
*1): Carry out the electrical discharge when Inverter parts are checked or replaced, refer to
, see on page 267
.