Pressing the “▲” pushbutton located under the TEMP indication on the remote control will display the following indication.
If the “▼” pushbutton is pressed, the prior indication is displayed.
Temperature Indication
Normal
(Thermistor Open-circuited
or PCB Defected)
(Temp. for Top of Comp.)
……Temperature Displayed
Abnormal
Indication of Category Code
Indication of Temperature, etc.
1
Indoor Unit Intake
Air Temp. at
Thermistor (ºC)
Indoor Unit
Discharge Air Temp.
at Thermistor (ºC)
2
Indoor Unit Heat
Exchanger Liquid
Pipe Temp. (Freeze
Protection) (ºC)
3
Outdoor Air Temp.
(ºC)
4
Indoor Heat
Exchanger Gas
Pipe Temp. (ºC)
5
Evaporating Temp.
at Heating (ºC)
6
Control Information
7
Discharge Gas
Temp. at the Top of
Comp. Chamber (ºC)
8
See "Self-Checking of PCBs using
Remote Control Switch"
(NOTE 1)
(NOTE 2)
During transient period such as starting time, etc.,
"- -" may be indicated for a limited time.
All the data during the check mode 2 will be
changed to "00" if a power failure occurs during
alarm indication.
to next page
- -
or
129
(Thermistor Short-circuited
or PCB Defected)
F F
or
255
(Temp. for Top of Comp.)
or
127
This is an indication for internal information for the
remote control switch.
This does not have any specific meaning.
The average temperature of running compressors
is indicated.
8 Troubleshooting
243
SMGB0065 rev. 1 - 12/2010
8