N O T E
•
Only the DIP DSW1, DSW2 and DSW4 switches can be set while the voltage supply is connected.
•
The symbol “■” indicates the position of the DIP switches. The figures show the position of the DIP switch once
the position setting has been completed.
•
With the DSW4 switch, the unit starts or stops after 10 to 20 seconds of the switch being activated.
•
Record the number of the outdoor unit to tell it apart from others during service and maintenance operations
in this area:
PSW1
PSW2
PSW3
PSW5
PSW4
PSW: Pushswitch on PCB1
PSW1: Enter.
PSW2, 3, 4 and 5: for checking.
DSW1, RSW1: refrigerant cycle number setting
•
Setting required.
•
Setting before RSW1 supply: 0.
•
Setting before DSW1 supply: 0 (digit of tens).
•
Set each outdoor unit number on each refrigerant cycle.
•
Outdoor and indoor units belonging to the same refrigerant cycle: set the
same cycle number in the outdoor and indoor units (indoor units: DSW5
and RSW2).
DSW1, RSW1: setting example for refrigerant cycle number 25
•
Maximum refrigerant cycle number setting: 63.
DSW2: capacity setting
Setting not required.
DSW3
Setting not required.
DSW4: test run and service settings
Setting required.
•
A: setting before supply.
•
B: refrigeration test run.
•
C: heating test run.
•
D: forced compressor stoppage.