Alarm code
05
Abnormal power source phase.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the main power source phase is reversely connected or one phase is not connected.
Correctly connect each phase
of power source.
No
Single Phase
(Is there any phase not connected?)
No
Yes
PCB1 is normal
PCB1 is normal
PCB1 is normal
Voltage for unit to
be suspended.
Running Voltage:
"B" V
Starting Voltage:
Less than "A" V
Abnormality with Power Source.
Is there any excessively voltage
decrease at power source?
Yes
Correctly connect each phase
of power source.
Faulty PCB1.
No
Reverse Phase Connection?
Yes
Check Item
Power Supply
“A”
“B”
400V / 50Hz
323
342 to 456
PCB1: Control PCB in Outdoor Unit
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Activation of
Reverse Phase
Sensor in
Outdoor Unit
Check it according
to electrical wiring
in item 4.3.4.
Replacing Wires, Repair,
Tightening Screws or
Correct Wiring
Reverse or Single Phase
Replace PCB1 if
faulty.
Faulty Outdoor Unit PCB1
8 Troubleshooting
183
SMGB0065 rev. 1 - 12/2010