Alarm code
07
Decrease in discharge gas superheat.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* In the case that the discharge gas superheat is less than 10 degrees on the upper part of the compressor is maintained
for 30 minutes, a retry operation is carried out. However, when the alarm occurs twice in two hours, the alarm code is
indicated.
Is the thermistor on
top of compressor
normal? *1)
Is superheat value
under 10°C?
Yes
Check the high-pressure
and compressor discharge
gas temperature and
calculate superheat value
by outdoor unit PCB1.
Remove sudden
fluctuation of load
like short path by
discharge air from
the outdoor unit, or
the cause of frequent
thermo-ON/OFF.
Faulty Thermistor
No
No
Is the thermistor
installed correctly
on the compressor?
Yes
Install it correctly.
No
Is it at cooling or
heating mode when the
alarm has occurred?
Is the connector on
indoor unit PCB for
expansion valve
connected properly?
Are the refrigerant
piping and electric
wiring matching?
Is refrigerant
correctly charged?
Is gas leaking?
Yes
Yes
Yes
Yes
Yes
Yes
Is superheat value
under 10°C?
Cooling
Check the high-pressure
and compressor discharge
gas temperature and
calculate superheat value
by outdoor unit PCB1.
Heating Operation
Cooling Operation
Heating
No
Plug the connectors
(*2) of PCB1
properly.
No
Charge correct
refrigerant volume.
Refer to TC.
No
Check the
expansion valve.
No
No
No
Match the
refrigerant piping
and electric wiring.
Plug the
connector properly.
Repair leaks of gas.
Correctly charge
refrigerant.
No
Is the opening of the
outdoor unit heat
exchanger's expansion
valve under 8%?
Are the connectors
(*2) of PCB1 of the
outdoor unit heat
exchanger's electric
expansion valve
connected properly?
Yes
Yes
*1): Refer to "Characteristics of Thermistor" of "Alarm Code 23".
*2): PCB1 Connector No. is shown in the below.
MV1
MVB
CN10
CN12
Position of Thermistor
THM8 (Td1)
for Inverter Drive
RAS-8FSXN to RAS-12FSXN
THM9 (Td2)
for Constant Speed Drive
RAS-14FSXN to RAS-18FSXN
PCB1: Control PCB in Outdoor Unit
8 Troubleshooting
186