(4) Inverter fin temperature increase protection control.
(5) Discharge temperature increase protection control.
(6) Discharge gas superheat decrease protection control.
Example of discharge temperature increase protection control:
A. Normal operation.
B. Forced decrease in frequency (1.0 Hz/s).
C. Not allowing frequency increases (only frequency decreases are
allowed).
D. Abnormal stoppage (cause of the stoppage d1-15).
(1)
For 5 seconds.
(2)
For 10 minutes.
N: normal.
D: degeneration.
5.2.11 Control of CH unit (CH-(6.0/10.0)N1)
The following table shows the expansion valve opening of CH unit at the steady condition.
The expansion valve opening right after the operation mode change (such as thermo-ON
→
thermo-OFF) may not be
matched with the table below. Make sure that the opening should be checked after at least 6 minutes of mode change.
(1) Checking Method of CH Unit Performance.
Check the LED on the PCB of CH unit to inspect the expansion value opening.
Refer to the table below for the relation between expansion valve opening and LED.
LED7
LED4
LED5
LED6
5 Control system
109
SMGB0065 rev. 1 - 12/2010
5