Alarm code
06
Abnormal Inverter voltage.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the voltage between terminal "P" and "N" of the transistor module (IPM) is insufficient
and occurs three times within a thirty minute period. If it occurs less than two times, a retry is carried out.
Direct Current
Measuring Position
Measuring Range: DC1000V
Does the voltage
fall during operation
by operation of
other apparatus?
Is connection correctly
between PCB2,
capacitors A*,
DCL and CMC?
Does LED201 on PCB2
ON after compressor's
electromagnetic switches
(CMC) turn ON?
Check capacitors A*.
Restart operation.
Check wiring and
wire sizes.
Connect correctly.
Replace capacitors.
Capacitors have high voltage.
Be careful especially. *1)
Yes
Yes
Yes
Check the wiring, the transistor
module and capacitors A*. *2)
In case the wiring is correct,
replace the transistor module.
Yes
Yes
Normal
Normal
Fault
Abnormal
(Loose Wiring,
Change of
Color)
Frequency can
increase higher
than 60Hz.
Compressor stops
immediately.
(lower than 30Hz)
Compressor stops
when frequency
increase. (Approx.
31Hz to 60Hz)
How is
compressor
operation?
Is the DC voltage
over B* V?
* Be careful especially because of high voltage.
Yes
No
No
No
No
No
No
Check CMC for Compressor.
Faulty transistor module.
Replace it.
Faulty CMC.
Replace it.
Faulty PCB2.
Replace it.
Is the power supply voltage 400V ±10%
Is the power supply voltage more than 323V?
Check Item
460
400V / 50Hz
Power Supply
CB1, CB2
B*
Voltage (DC)
A*
Capacitor
PCB1: Control PCB in Outdoor Unit
PCB2: Inverter PCB
<Outdoor Unit PCB1 Display Indication>
Abnormal of Inverter
Inverter
*1): If the capacitor has high voltage, carry out the high voltage discharge in accordance with procedures described in
chapter
Checking procedures for other main parts
, see on page 267
.
*2): The transistor module checking procedure is indicated in chapter
Checking procedures for other main parts
, see on
page 267
.
8 Troubleshooting
184