Voltage imbalance
Up to 3% in each phase, measured at the main terminal of the outdoor unit.
Electromagnetic compatibility
According to Directive 2004/108/EC (89/336/EEC) regarding electromagnetic compatibility, the following table indicates:
the maximum allowed impedance Z
max
of the system at the connection point of the user's power supply, as per
EN 61000-3-11.
Model
Z
max
(
Ω
)
Model
Z
max
(
Ω
)
RAS-8FSXN
–
RAS-14FSXN
0.11
RAS-10FSXN
–
RAS-16FSXN
0.11
RAS-12FSXN
–
RAS-18FSXN
0.08
Harmonics
In relation to IEC 61000-3-2 and IEC 61000-3-12, the situation of harmonics for each model is as follows:
Situation of the models in relation to IEC 61000- 3-2 and IEC
61000-3-12 Ssc "xx"
Model
Ssc "xx" (kVA)
Unit compliant with IEC 61000-3-2 (professional use).
RAS-8FSXN
–
RAS-10FSXN
Unit compliant with IEC 61000-3-12.
–
–
This unit is in accordance with Standard IEC 61000-3-12 with the condition
that the short circuit current Ssc is greater than or equal to xx (see Ssc
column) at the connection point between the power supply of the user and
the public grid. It is the responsibility of the installer or the user of the unit
to ensure, if necessary consulting the distribution grid operator, that the
unit is connected only to a power supply where the short circuit power is
greater than or equal to xx (see Ssc column).
RAS-14FSXN
5089
RAS-16FSXN
1593
RAS-18FSXN
1532
The authorities responsible for the electrical power supply can apply
restrictions relating to harmonics.
RAS-12FSXN
–
Unit(s) outside the scope of IEC 61000-3-12.
–
–
¿
Connection of outdoor units
Remove cover -G- to the refrigerant pipes -A-.
The power -C- and communication -B- cables should be inserted
in the unit through the pre-drilled holes and lower rubber bushing
-E- provided, using a different protective duct -F- for each one.
N O T E
Do not insert the supply and communication cables together
through the same protective duct. Keep a minimum distance
between them of 50 mm.
Fit the cover on the pipes -G- and completely seal access -D- of
the pipes to the unit, to prevent the entrance of water, rodents and
dirt.
Do not allow the cables to touch the refrigerant pipes, sharp metal edges or electric parts from inside the unit.
N O T E
•
Fasten the power cables with the flanges provided inside the unit.
•
Attach unused rubber bushings with adhesive.
•
Make a drainage hole in the lowest part of the protective duct.
C
G
D
D
D
F
B
E
E
A
4 Electrical wiring
74