A Outdoor unit failed
B Compressor
C
Even though one unit has failed, the other units can operate
continuously
N O T E
•
In order for the emergency operation may be used, two or
more outdoor units are required in the same refrigerant
cycle.
The emergency operation can be activated when the following alarm codes are displayed on the remote control screen:
Alarm code
Compressor type
Description of the failure
06
Failure of the compressor Inverter
Abnormal Inverter voltage
23
Abnormal discharge gas thermistor
48
Activation of the Inverter overcurrent protection
device
51
Abnormal Inverter current sensor
53
Inverter error signal detection
54
Abnormal Inverter radiator temperature
23
Failure of the constant speed compressor
Abnormal discharge gas thermistor on the upper part
of the compressor
39
Abnormal operating current in constant speed
compressor
Procedure (remote control PC-ART)
Simultaneously pressing the pushbuttons “TEMP” ▲ and ▼ -A- for
3 seconds will start the emergency operation mode. The message
EMG -B- is displayed on the remote control screen.
Operating condition
The emergency operation is not applicable to all compressors installed in the failed outdoor unit.
N O T E
•
The emergency operation is only available when all the indoor units and the connected remote controllers are
H-LINKII.
•
The emergency operation is only available when the alarm codes shown in the previous table are displayed.
•
The emergency operation is not available in case of failure of the inverter PCB or the fan controller.
B
B
B
C
x
A
PC-ART
A
B
8 Troubleshooting
154
SMGB0065 rev. 1 - 12/2010