Dimensions of flared pipe
Perform the widening operations in accordance with the
measurements shown below.
Diameters (mm)
A
+0
-0.4
(mm)
ø6.35
9.1
ø9.53
13.2
ø12.7
16.6
ø15.88
19.7
ø19.05
–
(1)
(1)
Not possible to perform the widening using pipe. In this case, use a connection with flare fitting.
Selection of the connection with flare fitting
It is not possible to perform the widening operation, if copper is used in pipes. In this case, use a connection with flare fitting.
Minimum thickness of the connection
Diameters (mm)
R410A
ø6.35
0.5
ø9.53
0.6
ø12.7
0.7
ø15.88
0.8
ø19.05
0.8
ø22.2
0.9
ø25.4
0.95
ø28.6
1.0
ø31.75
1.1
ø38.1
1.35
ø43.3
1.45
ø44.5
1.55
Distance between sides -B- of the nut -A-
Diameters (mm)
-B-
ø6.35
17
ø9.53
22
ø12.7
26
ø15.88
29
ø19.05
36
¿
Connection of pipes from the installation to the outdoor unit
1. Gas connection (low pressure) (only for heat recovery systems,
with CH units).
2. Gas connection (high pressure)
3. Liquid connection.
0.4-0.8R
45º ± 2º
øA
ød
90º±2
B
A
1
2
3
145
205
285
D
A
B
100
C
3 Piping work and
refrigerant charge
34
SMGB0065 rev. 1 - 12/2010