Alarm code
06
.
Abnormal fan controller voltage.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when voltage between terminal "R" and "S" of fan controller is insufficient and its occurence is
three times in 30 minutes. In the case that the occurrence is maller than 2 times, retry is performed.
Does the voltage
fall during operation
by operation of
other apparatus?
Is connection correctly
at fan controller?
Does LED201 on
fan controller ON?
Restart operation.
Check wiring and
wire sizes.
Connect correctly.
Yes
Yes
Yes
Yes
Yes
Fan revolution
can increase.
Fan stops
immediately.
Fan stops when
fan revolution is
increasing.
How is
fan motor
operation?
No
No
No
No
No
Faulty fan controller.
Replace it.
Is the power supply
voltage 220V+10% or
240V+10%?
Is the power supply
voltage more than
187V?
PCB1: Control PCB in Outdoor Unit
<Outdoor Unit PCB1 Display Indication>
Abnormal of Fan Controller
•
If fan controller has high voltage, perform the high voltage discharge work according to
, see on page 267
.
•
Check the wiring connection according to the checking procedure of fan controller indicated in the
, see on page 267
.
8 Troubleshooting
185
SMGB0065 rev. 1 - 12/2010