Incorrect Optional
Setting
The Comp.
does not Stop
or Start even
if the Setting
temperature
on LCD is
Changed *3)
Check Setting Condition
of "Thermistor of
Remote Control Switch"
by Optional Setting
* Setting and Control
"00":
"01":
"02":
Control by Indoor
Thermistor for
Suction Air
Control by
Thermistor of
Remote Control
Switch
Control by
Average Value of
Indoor Thermistor
for Suction Air
and Thermistor of
Remote Control
Switch
In case that
thermistor of remote
control switch is not
used, set at "00".
Incorrect
Input/Output Setting
Check Setting Condition
of "i1" and "i2" by
Input/Output Setting
* Setting and Control
"01":
"02":
Room Thermostat
(Cooling)
Room Thermostat
(Heating)
In case that room
thermostat is not
used, set for input
signal actually used.
If no signal is used,
set at "00".
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Self-checking of the remote control switch
, see on page 265
.
Troubleshooting in the check mode by using the remote control switch
, see on page 238
.
*3): Even if the controllers are correct, the compressor does not operate under the following conditions:
•
Indoor air temperature is lower than 19 °C or the outdoor air temperature lower than -5 °C during the cooling operation.
•
Indoor air temperature is higher than 30 °C or outdoor air temperature higher than 23 °C during the heating operation.
•
When the cooling (or heating) operation signal is sent to the outdoor unit and a different mode as heating (or cooling)
operation signal is sent to the indoor units.
•
When the demand or emergency stop signal is sent to the outdoor unit.
8 Troubleshooting