6.2 External input and output setting
The outdoor unit PCB has three input terminals (CN17, CN18) that receive external signals and two output terminals (CN16)
that send signals to the exterior.
The control functions are available by setting input and output terminals as shown below:
Control function number
Setting of input functions
1
Fixing the heating mode
2
Fixing the cooling mode
3
Demand stoppage
4
Outdoor unit fan motor start/stop
5
Forced stoppage
6
Control of 40% current demand
7
Control of 60% current demand
8
Control of 70% current demand
9
Control of 80% current demand
10
Control of 100% current demand
11
Low noise level setting 1
12
Low noise level setting 2
13
Low noise level setting 3
0
Without setting
Control function number
Configuration of output functions
1
Operating signal
2
Alarm signal
3
Compressor ON signal
4
Defrost signal
The following functions are set before shipment:
Name of the input terminal
Connector pin number
Setting function
Control function number
Input 1
CN17 (1-2)
Setting the heating mode
1
Input 2
CN17 (2-3)
Setting the cooling mode
2
Input 3
CN18 (1-2)
Stoppage demand
3
Name of the output terminal
Connector pin number
Setting function
Control function number
Output 1
CN16 (1-2)
Operating signal
1
Output 2
CN16 (1-3)
Alarm signal
2
6 Optional functions
115
SMGB0065 rev. 1 - 12/2010
6