7.1 Preliminary checks
The test run must be performed according to the instructions in section Test run.
D A N G E R
Do not use the system until all the checkpoints have been verified. As with the test run for the indoor unit, check
the Installation and maintenance manual for the indoor unit and the CH unit.
•
Make sure that the refrigerant pipes and the communication cables between the outdoor and indoor units are connected
to the same refrigerant cycle. Failure to do so could lead to abnormal operations or a serious accident. Check that the
setting of the refrigerant cycle DSW switches (DSW1 and RSW1 on outdoor units, DSW5 and RSW2 on indoor units)
and of the unit number (RSW) of the indoor units is suitable for the system. Check whether the DIP switch setting
specified on the printed circuit of the indoor and outdoor units is correct. Pay special attention to the outdoor unit number,
the refrigerant cycle number and the terminal resistance.
•
Make sure that the electric resistance is greater than 1 M
Ω
; to do this, measure the resistance between the earth and
the terminal of the electrical components. If not, do not use the system until the electrical leak has been detected and
repaired. Do not apply voltage to the communication terminals (Outdoor unit: TB2 1, 2, 3, 4 / Indoor unit: TB2 1, 2, A,
B / CH unit: TB2 1, 2, 3, 4).
•
Check that all the cables, L1, L2, L3 and N (R, S and T) are correctly connected to the power supply line. If they are not
correctly connected, the unit will not work and the remote control will indicate alarm code "05". When this happens,
check and change the phase of the power supply line according to the sheet on the back of the service cover.
C A U T I O N
Make sure that the unit's main power supply line switch has been on for more than 12 hours, to heat the compressor
oil with the heating resistors.
•
If several base units have been combined, stick the main unit label in a visible place (outdoor unit 1), so outdoor unit A
can be easily identified. Do not stick the main label on the secondary unit (outdoor units 2 and 3).
N O T E
1 Make sure the electric components in the installation (earth leakage breaker, circuit breaker, cables, connectors
and cable terminals) have been selected correctly in line with the electrical data given in this Manual. Also
ensure that these components meet the local and national codes.
2 Use shielded cables (> 0.75 mm
2
) for the communication installation wiring to avoid electromagnetic noise (the
shielded cable must have a total length shorter than 1000 m, and its size must comply with local codes).
3 Check the connection of the power supply wiring terminals (terminals “L1” to “L1” and “N” to “N”). AC supply
voltage 400 V. If it is different, some components could be damaged.
7 Test run
136
SMGB0065 rev. 1 - 12/2010