Alarm code
47
Activation of the low pressure decrease protection device (Vacuum operation protection).
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the suction pressure (Ps) is lower than 0.09 MPa for more than twelve minutes and this
condition occurs three or more times in one hour.
Is the amount of refrigerant correctly?
Yes
Yes
Is the outdoor stop valve open?
Is refrigerant leaking?
Check if connections of electric wiring
and refrigerant piping between the indoor
and outdoor unit are wrong.
Check the indoor expansion valve during cooling
and the outdoor expansion valve during heating.
Open the stop valve.
Correctly charge refrigerant.
Repair leaks.
No
No
Yes
Is suction pressure sensor normal?
Replace suction pressure sensor
if faulty.
No
No
Yes
Are the electronic expansion valves
fully closed and locked?
Check connection of the connectors
and the circuit board. Replace the
electronic expansion valves if faulty.
No
Yes
NOTE:
In the case of H-LINK system, check the refrigerant
system setting of the outdoor PCB1 and indoor PCB.
PCB1: Control PCB in Outdoor Unit
PCB: Indoor Unit PCB
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Check for conduction
after temperature of
outdoor fan motor is
decreased.
Faulty
Internal
Thermostat
Replace outdoor fan
motor.
Fault
Measure resistance
by tester.
Remove looseness
and replace connector.
Incorrect
Contact
Check connection.
Connect correctly.
Incorrect
Connection
Excessively
Low Suction
Pressure
(in Vacuum)
Internal
Thermostat for
Outdoor Fan
is Activated
in Heating
Operation
Measure coil resistance
and insulation resistance.
Replace outdoor fan
motor if faulty.
Faulty Outdoor Fan Motor
Check ref. charged
volume or check for
leakage.
Repair leakage and
correctly charge.
Shortage of Ref.
Check electrical
system and ref. cycle.
Correctly connect
between indoor unit
and outdoor unit.
Incorrect Connection
between Indoor Unit and
Outdoor Unit
Check connector
for PCB1.
Replace pressure
sensor if faulty.
Abnormal Low or High
Pressure Sensor
Check stop valve.
Open stop valve.
Closed Stop Valve
Check Td thermistors
for compressors and
measure Td thermistor
resistance.
Repair or replace
Td thermistor.
Closed Expansion Valve by
Disconnecting Td Thermistor
Check connector for
PCB.
Repair connector for
PCB or expansion valve.
Replace it if faulty.
Locked Expansion Valve
with Fully Closed
8 Troubleshooting
219
SMGB0065 rev. 1 - 12/2010
8