Setting Mode
If the inicial setting has to be modified, the following instructions must be followed:
1
Selecting “External Input and Output Setting” it will be displayed on the 7-segment display. (The setting must be carried
out during the stoppage of the outdoor unit. Also, the DSW4-#4 switch of the outdoor unit PCB must be set to “ON” before
the modification in order to prevent activation of the compressor).
A: Input/output terminal name.
B: Control function number.
N O T E
(*) This display shows the control function No. 1 (fixed heating operation mode) is set at input 1.
2
Pressing PSW2 and PSW4 changes the input/output terminal name. Once the input/output terminal is selected by
pressing PSW3 or PSW5, the control function number is modified.
PSW3
ON
PSW2
ON
PSW1
ON
3
After selecting Input/Output Terminal Name, press PSW3 or PSW5, and then choose Control Function No.
A
By pressing PSW3, the number increases by 1.
By pressing PSW5, the number decreases by 1.
(Control Function No.13
→
Press PSW3
→
return to 0)
4
After the function number is selected, press PSW1 for 3 seconds. The display will return to its normal indication. The
selected contents will be memorised in the outdoor unit's printed circuit board and the “External Input and Output Setting”
is completed. The memorised data is maintained even though the power supply is disconnected. The electrical wiring
diagram for each control function are described and the necessary parts are listed in
External input function setting
, see on
page 116
External output function setting
, see on page 120
.
6.2.1 External input function setting
The following signals can be received by the outdoor unit PCB.
B
A
SEG2
SEG1
A
6 Optional functions
116