The sound operation can be adjusted by selecting the control function number.
Control function number
Operating sound (targeted value)
Outdoor unit capacity (specification
ratio)
No setting
Catalogue value
100%
11 (Low noise level setting 1)
Catalogue value -2 dB(A)
80%
12 (Low noise level setting 2)
Catalogue value -5 dB(A)
60%
13 (Low noise level setting 3)
Catalogue value -8 dB(A)
40%
•
Short-circuit terminals 1 and 2 (input 3) of CN18 to set the low noise setting.
N O T E
•
The capacity of the outdoor unit will decrease because the compressor frequency and the outdoor unit fan
frequency necessarily decreases. The range of operation may be restricted.
•
In some cases, the sound operation (key values) can be temporarily higher than the values in the table.
X1
1
2
CN18
X
SS3
X1
a
b
c
d
a
3-pin connector
b
Outdoor unit PCB1
c
Control circuit
d
Power source
X1
Auxiliary relay
SS3
Demand current stoppage
Example: Low noise setting 2 during night time only:
A
Capacity
B
Operating sound
C
Daytime schedule
D
Nighttime schedule
E
Input terminal short-circuited
F
Catalogue value [dB(A)]
G
Catalogue value -5 dB(A)
6.2.2 External output function setting
The following signals can be received by the outdoor unit PCB.
6 Optional functions
120