10.11.2 Removing the solenoid valve coil (SVA, SVG)
1
Remove the screw -A- from the solenoid valve coil with a Philips
screwdriver. If it is difficult to remove the screw, use an
adjustable wrench or spanner.
2
Remove the solenoid valve coil -B- from the solenoid valve -C-.
10.11.3 Removing the solenoid valve
1
Remove the front service cover as described in the procedure
Removing the front service cover
, see on page 292
.
2
Close the following stop valves.
a
Heat pump system: Close the high pressure gas stop valve and the liquid stop valve.
b
Heat recovery system: Close the high pressure gas stop valve, the low pressure gas stop valve and the liquid stop
valve.
3
Collect the outdoor unit refrigerant from the low pressure check joint and the high pressure check joint. Make sure that
the pressure will not increase at this time.
N O T E
If the pressure increases, collect all the refrigerant in the refrigerant circuit.
4
Remove the solenoid valve coil as described in the procedure
Removing the solenoid valve coil (SVA, SVG)
, see on
page 314
.
5
Remove the welding from the following parts:
•
SVA -A- : 2 weld points -B-.
•
SVG -C-: 2 weld points per valve -D-.
A
B
C
D
A
B
C
D
RAS - (8-12) FSXN
RAS - (14-18) FSXN
N O T E
•
When welding, cover the solenoid valve with a wet cloth to avoid the heat.
•
Take care not to burn the wiring connections and the piping insulation when welding.
6
To fit the solenoid valve, carry out this procedure in reverse order.
A
B
C
10 Servicing
314
SMGB0065 rev. 1 - 12/2010