Place the refrigerant pipes of the outdoor units horizontally, or slightly tilted towards the side of the indoor units to prevent
the build-up of refrigerant oil at the lowest point -A-.
B
A
>500
If the refrigerant pipes are opposite the outdoor unit -A-, there should be a minimum of 500 mm between the outdoor units
and the connection kits -B- for maintenance operations.
N O T E
The 500 mm space is required when replacing the unit compressor.
± 15º
Install the connection kits parallel to the floor (± 15°).
3.1.5 General instructions on the installation of refrigerant pipes
The copper pipe used for the installation must be specific for refrigeration systems:
, see on page
30
.
The diameter of the refrigerant pipes depends directly on the power of the outdoor unit. The pipe diameter allocated must
be respected, in line with the instructions given in Chapter
.
The units must be located and the gas pipes laid, particularly when the outdoor unit is at a different height to the indoor unit,
in line with the instructions given in chapter
Precautions for the installation of the outdoor unit.
.
System performance depends on the distance between the outdoor and indoor unit. This aspect must be taken into account
for the installation of the refrigerant pipe. The outdoor units are factory-charged with sufficient refrigerant for a standard
installation of certain characteristics. Where the system installation requirements involve an increase in the distance
between the outdoor and indoor unit, refrigerant must be added to the installation in line with the instructions given in Chapter
.
3 Piping work and
refrigerant charge