Alarm code
11
Abnormal operation of thermistor for indoor unit inlet air temperature (air inlet thermistor).
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the thermistor is short-circuited (less than 0.24 kΩ) or cut (greater than 840 kΩ) during
the cooling or heating operation. The system automatically restarts when the fault is eliminated.
Yes
Yes
Connect it.
No
Faulty Thermistor
Faulty PCB
No
Is it connected to
THM1 (intake) of PCB?
Is resistance of THM1
between 0.24kΩ
and840kΩ?
Thermistor for
Air Inlet Temperature
(THM1)
In Case of 4-Way Cassette Type
PCB1: Control PCB in Outdoor Unit
PCB: Indoor Unit PCB
Cause
Check Item
Action
(Turn OFF Main Switch)
Phenomenon
Faulty Intake
Air Thermistor
Check resistance.
Replace thermistor
if faulty.
Fault
Check connection.
Connect wiring
correctly.
Incorrect Connection
Replace PCB and
check operation.
Replace PCB if faulty.
Faulty PCB
0
10
20
30
40
50
60
70
80
-15 -10 -5
0
5
10 15 20 25 30 35 40 45 50 55 60
82
61
46
35
27
20.5
16
12.5
10
8
5.3
3.6
2.5
90
Ambient Temperature (°C)
Thermistor
Resistance
(k
Ω
)
Thermistor Characteristics
<Outdoor Unit PCB1 Display Indication>
(Alarm Code 11~19)
Alarm Code (11~19)
Indoor Unit No.
for Failure
N O T E
This data is applicable to the following thermistors:
1 Outdoor unit discharge air temperature.
2 Indoor unit intake air temperature.
3 Indoor unit liquid piping temperature.
4 Indoor unit gas piping temperature.
5 Outdoor air temperature.
6 Outdoor unit liquid piping temperature.
7 Outdoor unit gas piping temperature.
8 Troubleshooting
193
SMGB0065 rev. 1 - 12/2010