10.11.4 Removing the reversing valve coil (RVR1, RVR2)
1
Remove the screw -A- from the reversing valve coil with a
Philips screwdriver. If it is difficult to remove the screw, use an
adjustable wrench or spanner.
2
Remove the reversing valve coil -B-.
10.11.5 Removing the reversing valve
1
Remove the front service cover as described in the procedure
Removing the front service cover
, see on page 292
.
2
Remove the electrical box, wiring and electrical box stay as described in the procedures
, see on page 295
Removing the electrical box for RAS-(14-18)FSXN
, see on page 295
the electrical box stay for RAS-(8-12)FSXN
, see on page 296
and
Removing the electrical box stay for RAS-
, see on page 296
.
3
Before starting with the task, collect the refrigerant from the refrigerant circuit into a cylinder and turn OFF the unit's
power supply line.
4
The position of the reversing valve -C- is shown in the figure.
5
Disconnect the wiring of the reversing valve coil.
6
Remove the reversing valve coil -B- (RVR1) and -D- (RVR2) as described in the procedure
, see on page 315
.
7
Remove the welding points -A- and cover the reversing valve with a wet cloth to avoid the heat.
RAS - (8-12) FSXN
RAS - (14-18) FSXN
N O T E
•
Remove only the welding -A- shown in the figure, otherwise leaks may occur when you fit the reversing
valve.
•
In the case of the heat pump system, connect the charge hose to the low pressure gas stop valve check
joint before removing the welding.
8
Remove the assembly of the reversing valve. Remove only the welding that is shown in the figure and cover the reversing
valve with a wet cloth to avoid the heat.
A
B
10 Servicing
315
SMGB0065 rev. 1 - 12/2010