Example of installation (38 HP: 2 pipes)
Connection of front or rear pipes
Lower pipe connection
A
B
C1
E
F
C2
E
G
H
D2
D1
I
I
A. Gas pipe (field-supplied).
B. Liquid pipe (field-supplied).
C1. Gas connection kit 1.
C2. Gas connection kit 2.
D1. Liquid connection kit 1.
D2. Liquid connection kit 2.
E. Accessory for connection of pipes (L-shaped).
F. Outdoor unit 1.
G. Outdoor unit 2.
H. Outdoor unit 3.
I. Accessory for connection of pipes (Z-shaped).
¿
Size of pipes (ø mm) and selection of multikit (2 pipes)
L3
L2
H2
H1
L2
H5
L5
A
(6)
(1)
L3
F
B
C
D
E
(3)
4
4
4
4
4
4
3
3
1
1
1
2
3
(6)
F
F
F
F
F
L3
L3
A: main outdoor unit
B, C: secondary outdoor units
D: connection kit 1
E: connection kit 2
F: indoor units
Size of pipes
1. Pipe diameter for the outdoor unit.
2. Diameter of the main pipe (from the base unit or connection kit 1 to the first branch)
(2)
.
HP outdoor unit
Equivalent pipe length < 100 m
HP outdoor unit
Equivalent pipe length < 100 m
Gas
Liquid
Gas
Liquid
8
ø19.05
ø9.53
(18-24)
ø28.6
ø15.88
10
ø22.2
ø9.53
(26-34)
ø31.75
ø19.05
(12/14)
ø25.4
ø12.7
(36-54)
ø38.1
ø19.05
16
ø28.6
ø12.7
—
—
—
3. Pipe diameter after first branch
(3)
.
Total HP indoor unit
Gas
Liquid
Total HP indoor unit
Gas
Liquid
< 6
ø15.88
ø9.53
(16-17.99)
ø28.6
ø12.7
(6-8.99)
ø19.05
ø9.53
(18-25.99)
ø28.6
ø15.88
(9-11.99)
ø22.2
ø9.53
(26-35.99)
ø31.75
ø19.05
(12-15.99)
ø25.4
ø12.7
> 36
ø38.1
ø19.05
3 Piping work and
refrigerant charge