(b) Regarding the retry control, the lastest retry code will be indicated unless the protection control related with the frequency
control is indicated.
Code
Protection control
Code during the
degeneration control
P
0
1
Pressure ratio protection control
P
c
1
P
0
2
High pressure increase protection
P
c
2
P
0
3
Inverter current protection
P
c
3
P
0
4
Inverter fin temperature increase protection
P
c
4
P
0
5
Discharge gas temperature increase protection at the upper part of
the compressor
P
c
5
P
0
6
Low pressure decrease protection
Without
P
0
9
High pressure decrease protection
P
0
A
Demand current protection control
P
0
d
Low pressure increase protection
Code
Retry control
Code during
the
degeneration
control
P
1
1
Pressure ratio decrease retry
Without
P
1
2
Low pressure increase retry
P
1
3
High pressure increase retry
P
1
4
Constant speed compressor overcurrent retry
P
1
5
Discharge gas temperature increase retry / Low pressure decrease retry
P
1
6
Discharge gas super-heat decrease retry
P
1
7
Inverter anomaly retry
P
1
8
Abnormal Inverter voltage retry / Inverter failure retry
P
2
6
High pressure decrease retry
N O T E
(1) The retry indication is prolonged for 30 minutes unless a protection control is indicated.
(2) The retry indication disappears if the stop signal comes from all rooms.
(3) The protection control code indicated on the 7 segment display changes to an alarm code when the abnormal
operation occurs. Also, the same alarm code is indicated on the remote control.
(4) In the case that the degeneration control is activated, indications Pc1 to Pc5 are displayed instead of P01 to
P05.
8 Troubleshooting
246
SMGB0065 rev. 1 - 12/2010