(6) Check method by checking mode
To Start Checking
Press PSW1 for once.
(A) Outdoor Combination Unit No.
Unit
Indication
PrT0
PrT2
PrT3
Unit A (No.1)
Unit B (No.2)
Unit C (No.3)
Menu
Connecting Information
Outdoor Unit Information
Indoor Unit Information
Cause of Alarm Code
History of Alarm Code
The Details of indicated informations
shall be according to the (B)
“Connecting Information”.
The Details of indicated informations
shall be according to the (C)
“Outdoor Unit Information”.
The Details of indicated informations
shall be according to the (D)
“Indoor Unit Information”.
The Details of indicated informations
shall be according to the (E)
“Cause of Alarm Code Information”.
The Details of indicated informations
shall be according to the (F)
“Alarm Code History Information”.
Check Mode
“CHEC”
External
Input/Output
“ioST”
Function
Setting
“FUNC”
The outdoor combination unit No. is
indicated on the 7-segment display as follows.
Indication Example
Unit A (No.1)
Details of External
Input/Output Setting is shown
in item 4.2.
And Function Setting is shown
in item 4.3.
Press PSW1 more than
3 seconds.
“Menu” will be indicated.
PSW1
PSW2
PSW3
PSW5
PSW4
PSW pushswitch on PCB1
PSW1: enter.
PSW2, 3, 4 and 5: for checking.
•
To cancel the check method.
Press PSW1 for more than three seconds while the “menu mode” is displayed.
The indication on the LCD screen will be turned OFF and condition will return to normal.
N O T E
Ensure the check mode is cancelled after the checks have been carried out.
(B) Connection information
This information is indicated on unit A (main unit) only.
Press PSW4 (▼) to move forward or PSW2 (▲) to move back.
Select the outdoor unit No. for indication.
Press PSW3 (►) for detailed information on the selected unit No.:
Unit
Indication
Unit A (No. 1)
od00
Unit B (No. 2)
od02
Unit C (No. 3)
od03
Press PSW4 (▼) to move forward or PSW2 (▲) go back.
This information will be alternatively indicated as “Item”
→
“Details”.
8 Troubleshooting
249
SMGB0065 rev. 1 - 12/2010
8