Forced stoppage (Control function number 5)
•
When the outdoor unit PBC1 input terminals for the forced stoppage are short-circuited during running the compressor
and the indoor unit fans are stopped. However, the remote control screen remains in the same number 10 stoppage
code. In this case, if the input terminals are open, the operation is resumed.
•
Short-circuit terminals 1 and 2 (input 3) of CN18 to set the forced stoppage.
X1
1
2
1
2
3
CN18
SS3
X1
a
b
c
d
a
3-pin connector
b
Outdoor unit PCB1
c
Control circuit
d
Power source
X1
Auxiliary relay
SS3
Forced stoppage switch
¿
Demand current control of 40, 60, 70, 80 and 100% (Control function number 6 to 10)
•
When the demand current control input terminals for the outdoor unit PCB1 are short-circuited, the compressor
frequency is controlled by the maximum current limit of the outdoor unit, which is set at 100%, 80%, 70%, 60% and
40%. The maximum running current of the outdoor unit will be selected as described in procedure
, see on page 115
.
•
Short-circuit terminals 1 and 2 (input 3) of CN18 to configure the current demand.
•
If the running current of the outdoor unit increases above the limit, the indoor unit is put in Thermo-OFF condition.
Stoppage code number 10 is shown. When the input terminal is opened during the demand current control, control is
re-established.
X1
1
2
1
2
3
CN18
SS3
X1
a
b
c
d
a
3-pin connector
b
Outdoor unit PCB1
c
Control circuit
d
Power source
X1
Auxiliary relay
SS3
Demand current switch
¿
Low noise setting 1, 2, 3 (Control function number 11 to 13)
•
When the input terminals for low noise setting of the outdoor unit PCB1 are short-circuited, the frequency of the
compressor and the fan rotation frequency are controlled and the outdoor unit operating sound is within the values
shown in the table: