Additional values give more detailed information about the signal condition:
“GREEN” (No fault), “YELLOW” (Unclear), or “RED” (broken rotor bar detected) statuses are displayed in real time.
Under a Yellow signal condition, any one of the following signal conditions may be display for clarity:
•
“INVALID_FREQUENCY”; The frequency with +-0.1 of the nominated frequency is required.
•
“INVALID_DATA”: Such as two consecutive zeros.
•
“UNSTABLED_SIGNAL”; - The stability of the signal is required.
•
“UNSTABLED_FREQUENCY”; - The stability of the frequency is required.
•
“INSUFFICIENT_LOAD” - At least 85% of the full load is required.
The time between the BBD is selectable. The default is 3600 sec.
Device Planning Parameters of the Motor Wellness
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]