EMR-4000
IM02602009E
Overview of Slots - Assembly Groups
In line with the customers' requirement, the devices are combined in a
modular way (in compliance with the order code). In each of the slots, an
assembly/group may be integrated. In the following diagram, the terminal
assignment of the individual assembly/groups are shown. The exact
installation/placement of the individual modules can be determined from
the connection diagram attached to the top of your device.
Overview of Slots
Housing
B2
Schematic Diagram
The housing must be carefully grounded. Connect a ground cable (AWG
12-10 [4 to 6 mm
2
] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is
marked with the ground symbol (at the rear side of the device).
The power supply card needs a separate ground connection (AWG 14
[2.5 mm
2
] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.
www.eaton.com
28
X1
X2
X3
X100
X102
X5
X6
X104
X4
X103
Slot3
Slot4
Slot5
Slot6
Slot1
Slot2
X101