51P - Overcurrent Protection [51, 51C, 51V]
Available stages:
51P[1] ,51P[2] ,51P[3]
If you are using inrush blockings the tripping delay of the current protection
functions must be at least 30ms or more in order to prevent faulty trippings.
In order to ensure correct functioning of the directional detection after single-phase
short-circuits, the following reference voltage is used: For phase current
IA it is the
line-to-line voltage
VBC, for phase current IB the line-to-line voltage VCA and for
phase current
IC the line-to-line voltage VAB.
In case the fault happens to be near the measuring location and there is no reference
voltage for directional recognition available any more (neither measured or from
history (voltage memory)), then the module will - depending on the parameter setting -
either trip non-directional or it will be blocked.
All overcurrent protective elements are identically structured.
This module offers Adaptive Parameter Sets.
Parameters can be modified within parameter sets dynamically by means of
Adaptive Parameter Sets.
Please refer to chapter Parameter / Adaptive Parameter Sets.
The following table shows the application options of the Overcurrent Protection element
Applications of the 51P-Protection Module Setting in
Option
ANSI 51 – Short circuit protection, non-
directional
Device Planning menu
Criterion: Fundamental/TrueRMS
ANSI 51V – Voltage restraint overcurrent
protection
Parameter Set:
VRestraint = active
Criterion: Fundamental/TrueRMS
51C Voltage controlled overcurrent protection
(
Please refer to the chapter
Parameter/Adaptive Parameter
)
Adaptive Parameters
Criterion: Fundamental/TrueRMS
www.eaton.com
510
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...