EMR-4000
IM02602009E
Setting Group Parameters of the BF
In order to prevent a faulty activation of the BF Module, the pickup (alarm)
time must be greater than the sum of:
Operating time of the protective relay
+The close-open time of the breaker (please refer to the technical data of
the manufacturer of the breaker);
+Drop off time (current- or position indicators)
+Security margin.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/BF]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/BF]
I-BF >
Breaker Failure Alarm will be initiated if this threshold is
still exceeded after the timer has expired (50 BF).
Only available if: Scheme50BF = Or Scheme = 50BF and
CB Pos
0.02 - 4.00In
0.02In
[Protection Para
/<1..4>
/Supervision
/BF]
t-BF
If the delay time is expired, an BF alarm is given out.
0.00 - 10.00s
0.20s
[Protection Para
/<1..4>
/Supervision
/BF]
www.eaton.com
748
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...