EMR-4000
IM02602009E
Control Parameters
Direct commands of the Control Module
Parameter
Description
Setting range
Default
Menu path
Switching Authority Switching Authority
None,
Local,
Remote,
Local and Remote
Local
[Control
/General Settings]
Signals of the Control Module
Signal
Description
Local
Switching Authority: Local
Remote
Switching Authority: Remote
SG Indeterm
Minimum one Switchgear is moving (Position cannot be determined).
SG Disturb
Minimum one Switchgear is disturbed.
Counters of the Control Module
Parameter
Description
CES SAuthority
Command Execution Supervision: Switching Command not executed. No switching authority.
CES DoubleOperating
Command Execution Supervision: A second switch command is in conflict with a pending one.
No. of rej. Com
No. of rej. Com because Locked by ParaSystem
www.eaton.com
436