Each protection element generates its own pickup and trip signals, which are automatically passed onto the
»Prot«
module where the phase based and general (collective) pickup and trip signals are generated. The
»Prot« module
serves as a top level and a common place to group all pickups and trips from each individual protection element.
For instance, »P
ROT
.P
ICKUP
P
HASE
A« is the phase A pickup signal OR-ed from all protection elements; »P
ROT
.T
RIP
P
HASE
A« is the phase A trip signal OR-ed from all protection elements; »P
ROT
.P
ICKUP
« is the collective pickup signal OR-ed
from all protection elements; Prot.Trip is the collective Trip signal OR-ed from all protection elements, and etc. The
Tripping commands of the protection elements have to be fed to the
»Bkr Manager« module for further trip request
processing.
The tripping commands are executed by the
»Bkr Manager«
module.
Tripping commands have to be assigned to a breaker. The Breaker Manager will
issue the trip command to the breaker.
If a protection element is activated and respectively decides to trip, two pickup signals will be created.
1.
The module or the protection element issues an pickup/alarm (e.g.: »50P[1].P
ICKUP
« or »50P[1].T
RIP
«).
2. The master
»Prot« module
collects/summarizes the signals and issues
a pickup/alarm or
a trip
signal
»P
ROT
.P
ICKUP
« »P
ROT
.T
RIP
«.
www.eaton.com
391
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...