EMR-4000
IM02602009E
The screen shot above shows the adaptive setting configurations following applications based on only one simple
overcurrent protection element:
1.
Standard Set: Default settings;
2.
Adaptive Set 1:
SOTF application (Switch-OnTo-Fault);
3.
Adaptive Set 2:
CLPU application (Cold Load Pickup);
Application Examples
The output signal of the
Switch OnTo Fault module can be used to activate an
Adaptive Parameter Set
that
sensitizes the overcurrent protection.
The output signal of the
Cold Load Pickup module can be used to activate an
Adaptive Parameter Set
that
desensitizes the overcurrent protection.
By means of
Adaptive Parameter Sets,
an Adaptive
Auto Reclosure can be realized. After a reclosure attempt, the
tripping thresholds or tripping curves of the overcurrent protection can be adapted.
Depending on undervoltage, the overcurrent protection can be modified (voltage controlled). This applies to devices
that offer voltage protection only.
The ground overcurrent protection can be modified by the residual voltage. This applies to devices that offer voltage
protection only.
Dynamic and automatic adaption of the ground current settings in order to adapt the settings to different loads
(single-phase load diversity).
Adaptive Parameter Sets are only available for devices with current
protection modules.
www.eaton.com
358
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...