Parameter Set Parameters of the Reactive Power Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
32V[1]: Inactive
32V[2]: Active
32V[3]: Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
LOP Blo
Measuring Circuit Supervision Voltage
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
CTS Blo
Measuring Circuit Supervision Current
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Pickup Q>
Over(load) Reactive Power Pickup Value. Monitoring the
maximum allowed reactive power of the electrical
equipment like transformers or overhead lines). If the
maximum value is exceeded, a condensator bank could
be switched off. Definition for Sn is as follows: Sn =
1.7321 * VT rating * CT rating. The voltage is the line-to-
line voltage.
Only available if: Device Planning: PQS.Mode = Pickup
Q>
0.003 - 10.000VAn
1.20VAn
[Protection Para
/<1..4>
/Power-Prot
/32V[1]]
www.eaton.com
663
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...