EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
Scale Factor 0
The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP
/Point map
/Analog Input]
Dead Band 0
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP
/Point map
/Analog Input]
Analog value 1
Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList
-.-
[Device Para
/DNP
/Point map
/Analog Input]
Scale Factor 1
The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP
/Point map
/Analog Input]
Dead Band 1
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP
/Point map
/Analog Input]
Analog value 2
Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList
-.-
[Device Para
/DNP
/Point map
/Analog Input]
www.eaton.com
310
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...