EMR-4000
IM02602009E
System Alarms
Available Elements:
SysA
Within the System Alarms menu [SysA] the User can configure:
General Settings (activate/inactivate the Demand Management, optional assign a signal, that will block the Demand
Management);
Power Protection (please refer to section 32, 32V, 32VA);
Demand Management (Power and Current); and
THD Protection.
Please note, that all thresholds are to be set as primary values.
Demand Management
Demand is the average of system current or power over a time interval (window)
. D
emand management supports the
User to keep energy demand below target values bound by contract (with the energy supplier). If the contractual target
values are exceeded, extra charges are to be paid to the energy supplier.
Therefore, demand management helps the User detect and avoid averaged peak loads that are taken into account for
the billing. In order to reduce the demand charge respective to demand rate, peak loads, if possible, should be
diversified. That means, if possible, avoiding large loads at the same time. In order to assist the User in analyzing the
demand, demand management might inform the User by an alarm. The User might also use demand alarms and
assign them on relays in order to perform load shedding (where applicable).
Demand management comprises:
Watt Demand (Active Power);
VAr Demand (Reactive Power);
VA Demand (Apparent Power); and
Current Demand.
www.eaton.com
170
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...