EMR-4000
IM02602009E
Zone Interlocking
Only for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor
output): 5 Vdc, <2mA for connection to electronic inputs only.
Zone Out:
Output voltage (High)
4.75 to 5.25 Vdc
Output voltage (Low)
0.0 to +0.5 Vdc
Zone In:
Nominal input voltage
+5 Vdc
Max. input voltage
+5.5 Vdc
Switching threshold ON
min. 4.0 Vdc
Switching threshold OFF
max. 1.5 Vdc
Galvanic isolation
2.5 kV ac (to ground and other IO)
Connection:
Screw-type terminals (twisted pair)
www.eaton.com
837
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...