EMR-4000
IM02602009E
Statistics
Statistics
In menu
»Operation/Statistics« the min., max. and mean values of the measured and calculated measured quantities
can be found.
Configuration of the Minimum and Maximum Values
The calculation of the minimum and maximum values will be started:
When a Reset signal becomes active (Min/Max)
When the device is restarted
After configuration
Minimum and Maximum Values (Peak Values/Pointers)
Time interval for the calculation of the
minimum and maximum values
Reset
Configuration Options
Where to configure?
Within menu [Device Para\
Statistics\
Min/Max]
The minimum and maximum values will
be reset with the rising edge of the
corresponding reset signal.
Res Min
Res Max
(e.g. via digital Inputs). These signals will reset
the minimum and maximum pointers.
Display of Minimum Values
Where? Within menu [Operation\Statistics\Min]
Display of Maximum Values
Where? Within menu [Operation\Statistics\Max]